CertiFiber Pro custom test limit: Difference between revisions
No edit summary |
No edit summary |
||
(5 intermediate revisions by the same user not shown) | |||
Line 2: | Line 2: | ||
== Introduction == | == Introduction == | ||
As application limits continue to become more stringent, limits proposed by ISO and ANSI are | As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. Using recent ISO and ANSI test limits is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in data centers. | ||
| | ||
Line 8: | Line 8: | ||
== Solution == | == Solution == | ||
Use | Use these custom limits for length/loss testing of LC, SC, ST, FC and E2000 terminated fiber optic links. | ||
Users could decide to set optional Length and Overall Loss limit in accordance with the application. For example: if the link is OM3 multimode fiber and the application is IEEE 10GBASE-SR, these values could be respectively 300m and 2,60dB (@ 850nm). | |||
More information on the use of custom limits is available during the Certified Cabling Test Training module VERSIVFO. | More information on the use of custom limits is available during the Certified Cabling Test Training module VERSIVFO. | ||
Line 21: | Line 21: | ||
|- | |- | ||
| Length (m) | | Length (m) | ||
| 2000 | | 2000 or 5000 | ||
| | | N/A | ||
|- | |- | ||
| Connection Loss (dB) | | Connection Loss (dB) | ||
Line 42: | Line 42: | ||
| Loss/km @ 1310nm (dB/km) | | Loss/km @ 1310nm (dB/km) | ||
| 1,00 | | 1,00 | ||
| | | 0.40 | ||
|- | |- | ||
| Loss/km @ 1550nm (dB/km) | | Loss/km @ 1550nm (dB/km) | ||
| 1,00 | | 1,00 | ||
| | | 0.40 | ||
|} | |} |
Latest revision as of 06:58, 8 May 2021
Introduction
As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. Using recent ISO and ANSI test limits is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in data centers.
Solution
Use these custom limits for length/loss testing of LC, SC, ST, FC and E2000 terminated fiber optic links.
Users could decide to set optional Length and Overall Loss limit in accordance with the application. For example: if the link is OM3 multimode fiber and the application is IEEE 10GBASE-SR, these values could be respectively 300m and 2,60dB (@ 850nm).
More information on the use of custom limits is available during the Certified Cabling Test Training module VERSIVFO.
Parameter | Default value | Recommended value |
Length (m) | 2000 or 5000 | N/A |
Connection Loss (dB) | 0,75 | 0,30 |
Splice Loss (dB) | 0,30 | 0,15 |
Loss/km @ 850nm (dB/km) | 3,00 | 3,00 |
Loss/km @ 1300nm (dB/km) | 1,50 | 1,50 |
Loss/km @ 1310nm (dB/km) | 1,00 | 0.40 |
Loss/km @ 1550nm (dB/km) | 1,00 | 0.40 |