OptiFiber Pro custom test limit: Difference between revisions
No edit summary |
No edit summary |
||
(32 intermediate revisions by the same user not shown) | |||
Line 2: | Line 2: | ||
== Introduction == | == Introduction == | ||
As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. Using recent ISO and ANSI test limits is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in datacenters. | |||
| | ||
Line 10: | Line 8: | ||
== Solution == | == Solution == | ||
We stronly recommend upgrading to Versiv firmware version 6.8 before continuing. Unless specified otherwise, use these values to create one custom limit for testing PC/UPC terminated links and a second custom limit for testing APC terminated links. Please remember that in case of OTDR, "Connector Loss" should be interpreted as "Reflective Event Loss" and "Splice Loss" as "Non reflective Event Loss". | |||
| | ||
=== Maximum length for PC, UPC and APC terminated links === | === Maximum length for <span style="background-color:#00FFFF">PC</span>, <span style="background-color:#00FFFF">UPC</span> and <span style="background-color:#FFFF00">APC</span> terminated links === | ||
{| | {| border="1" cellpadding="1" cellspacing="1" style="width: 800px" | ||
|- | |- | ||
! scope="col" style="width: 332px" | Parameter | ! scope="col" style="width: 332px" | Parameter (m) | ||
! scope="col" style="width: 455px" | Recommended value | ! scope="col" style="width: 455px" | Recommended value | ||
|- | |- | ||
| style="width: 332px" | Length | | style="width: 332px" | Length | ||
| style="width: 455px; | | style="width: 455px; text-align: right" | N/A | ||
|} | |} | ||
| | ||
=== General Settings for PC, UPC and APC terminated links === | === General Settings for <span style="background-color:#00FFFF">PC</span>, <span style="background-color:#00FFFF">UPC</span> and <span style="background-color:#FFFF00">APC</span> terminated links === | ||
{| | {| border="1" cellpadding="1" cellspacing="1" style="width: 800px" | ||
|- | |- | ||
! scope="col" | Parameter | ! scope="col" | Parameter | ||
Line 35: | Line 33: | ||
! scope="col" | 1300nm | ! scope="col" | 1300nm | ||
! scope="col" | 1310nm | ! scope="col" | 1310nm | ||
! scope="col" | | ! scope="col" | 1490nm | ||
! scope="col" | 1550nm | ! scope="col" | 1550nm | ||
! scope="col" | | ! scope="col" | 1625nm | ||
|- | |- | ||
| Overall Loss (Max) | | Overall Loss (Max) (dB) | ||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
|- | |- | ||
| Overall Loss (Min) | | Overall Loss (Min) (dB) | ||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
|- | |- | ||
| Optical Return Loss | | Optical Return Loss (dB) | ||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
|- | |- | ||
| Segment Attenuation Coefficient (Max) | | Segment Attenuation Coefficient* (Max) (dB/km) | ||
| style="text-align: right" | 3.0 | | style="text-align: right" | N/A (3.0) | ||
| style="text-align: right" | 1.5 | | style="text-align: right" | N/A (1.5) | ||
| style="text-align: right" | | | style="text-align: right" | N/A (0.4) | ||
| style="text-align: right" | | | style="text-align: right" | N/A (0.4) | ||
| style="text-align: right" | | | style="text-align: right" | N/A (0.4) | ||
| style="text-align: right" | | | style="text-align: right" | N/A (0.4) | ||
|- | |- | ||
| Segment Attenuation Coefficient (Min) | | Segment Attenuation Coefficient (Min) (dB/km) | ||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
|} | |} | ||
(*) Accurate measurements of Segment Attenuation Coefficient requires a long fiber. Therefore, it is recommended to set this limit to N/A (not applicable) for multi-mode and short singlemode segments. If you have to enforce a limit, use the recommended values between brackets, but first try to explain to your customer/supplier why this is not a good idea. | |||
| | ||
=== Event Settings for PC | === Event Settings for <span style="background-color:#00FFFF">PC</span><span style="background-color:#00FFFF">/UPC</span> terminated links === | ||
{| | {| border="1" cellpadding="1" cellspacing="1" style="width: 800px" | ||
|- | |- | ||
! scope="col" | Parameter | ! scope="col" | Parameter (dB) | ||
! scope="col" | 850nm | ! scope="col" | 850nm | ||
! scope="col" | 1300nm | ! scope="col" | 1300nm | ||
! scope="col" | 1310nm | ! scope="col" | 1310nm | ||
! scope="col" | | ! scope="col" | 1490nm | ||
! scope="col" | 1550nm | ! scope="col" | 1550nm | ||
! scope="col" | | ! scope="col" | 1625nm | ||
|- | |- | ||
| Connector Loss (Max) | | Connector Loss (Max) | ||
| style="text-align: right" | 0.30 | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | 0.30 | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | 0.30 | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | 0.30 | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | | | style="text-align: right" | 0.30-0.50 | ||
|- | |- | ||
| Connector Loss (Min) | | Connector Loss (Min) | ||
Line 106: | Line 106: | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | |||
|- | |- | ||
| Splice Loss (Max) | | Splice Loss (Max) | ||
Line 114: | Line 114: | ||
| style="text-align: right" | 0.15 | | style="text-align: right" | 0.15 | ||
| style="text-align: right" | 0.15 | | style="text-align: right" | 0.15 | ||
| style="text-align: right" | 0.15 | | style="text-align: right" | 0.15 | ||
| style="text-align: right" | | | style="text-align: right" | 0.15 | ||
| style="text-align: right" | 0.15 | |||
|- | |- | ||
| Splice Loss (Min) | | Splice Loss (Min) | ||
Line 122: | Line 122: | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | |||
|- | |- | ||
| Reflectance (Max) | | Reflectance (Max) | ||
Line 130: | Line 130: | ||
| style="text-align: right" | -35.00 | | style="text-align: right" | -35.00 | ||
| style="text-align: right" | -45.00 | | style="text-align: right" | -45.00 | ||
| style="text-align: right" | -45.00 | | style="text-align: right" | -45.00 | ||
| style="text-align: right" | | | style="text-align: right" | -45.00 | ||
| style="text-align: right" | -45.00 | |||
|- | |- | ||
| Reflectance (Min) | | Reflectance (Min) | ||
Line 138: | Line 138: | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | |||
|} | |} | ||
| | ||
=== Event Settings for APC terminated links === | === Event Settings for <span style="background-color:#FFFF00">APC</span> terminated links === | ||
{| | {| border="1" cellpadding="1" cellspacing="1" style="width: 800px" | ||
|- | |- | ||
! scope="col" | Parameter | ! scope="col" | Parameter (dB) | ||
! scope="col" | 850nm | ! scope="col" | 850nm<sup>#</sup> | ||
! scope="col" | 1300nm | ! scope="col" | 1300nm<sup>#</sup> | ||
! scope="col" | 1310nm | ! scope="col" | 1310nm | ||
! scope="col" | | ! scope="col" | 1490nm | ||
! scope="col" | 1550nm | ! scope="col" | 1550nm | ||
! scope="col" | | ! scope="col" | 1625nm | ||
|- | |- | ||
| Connector Loss (Max) | | Connector Loss (Max) | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | 0.30 | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | 0.30 | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | | | style="text-align: right" | 0.30-0.50 | ||
|- | |- | ||
| Connector Loss (Min) | | Connector Loss (Min) | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | |||
|- | |- | ||
| Splice Loss (Max) | | Splice Loss (Max) | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | 0.30 | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | 0.30 | | style="text-align: right" | 0.30-0.50 | ||
| style="text-align: right" | | | style="text-align: right" | 0.30-0.50 | ||
|- | |- | ||
| Splice Loss (Min) | | Splice Loss (Min) | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | |||
|- | |- | ||
| Reflectance (Max) | | Reflectance (Max) | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | -65.00 | | style="text-align: right" | -65.00** | ||
| style="text-align: right" | | | style="text-align: right" | -65.00** | ||
| style="text-align: right" | -65.00 | | style="text-align: right" | -65.00** | ||
| style="text-align: right" | | | style="text-align: right" | -65.00** | ||
|- | |- | ||
| Reflectance (Min) | | Reflectance (Min) | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | | style="text-align: right" | N/A | ||
| style="text-align: right" | | | style="text-align: right" | N/A | ||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | |||
| style="text-align: right" | N/A | |||
|} | |} | ||
( | (#) APC style connectors aren't used in combination with multi-mode fibers. | ||
(**) For older generations (existing) APC connections, a value of -55.00dB may be more appropriate. |
Latest revision as of 12:22, 25 August 2023
Introduction
As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. Using recent ISO and ANSI test limits is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in datacenters.
Solution
We stronly recommend upgrading to Versiv firmware version 6.8 before continuing. Unless specified otherwise, use these values to create one custom limit for testing PC/UPC terminated links and a second custom limit for testing APC terminated links. Please remember that in case of OTDR, "Connector Loss" should be interpreted as "Reflective Event Loss" and "Splice Loss" as "Non reflective Event Loss".
Maximum length for PC, UPC and APC terminated links
Parameter (m) | Recommended value |
---|---|
Length | N/A |
General Settings for PC, UPC and APC terminated links
Parameter | 850nm | 1300nm | 1310nm | 1490nm | 1550nm | 1625nm |
---|---|---|---|---|---|---|
Overall Loss (Max) (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
Overall Loss (Min) (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
Optical Return Loss (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
Segment Attenuation Coefficient* (Max) (dB/km) | N/A (3.0) | N/A (1.5) | N/A (0.4) | N/A (0.4) | N/A (0.4) | N/A (0.4) |
Segment Attenuation Coefficient (Min) (dB/km) | N/A | N/A | N/A | N/A | N/A | N/A |
(*) Accurate measurements of Segment Attenuation Coefficient requires a long fiber. Therefore, it is recommended to set this limit to N/A (not applicable) for multi-mode and short singlemode segments. If you have to enforce a limit, use the recommended values between brackets, but first try to explain to your customer/supplier why this is not a good idea.
Event Settings for PC/UPC terminated links
Parameter (dB) | 850nm | 1300nm | 1310nm | 1490nm | 1550nm | 1625nm |
---|---|---|---|---|---|---|
Connector Loss (Max) | 0.30-0.50 | 0.30-0.50 | 0.30-0.50 | 0.30-0.50 | 0.30-0.50 | 0.30-0.50 |
Connector Loss (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Splice Loss (Max) | 0.15 | 0.15 | 0.15 | 0.15 | 0.15 | 0.15 |
Splice Loss (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Reflectance (Max) | -35.00 | -35.00 | -45.00 | -45.00 | -45.00 | -45.00 |
Reflectance (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Event Settings for APC terminated links
Parameter (dB) | 850nm# | 1300nm# | 1310nm | 1490nm | 1550nm | 1625nm |
---|---|---|---|---|---|---|
Connector Loss (Max) | N/A | N/A | 0.30-0.50 | 0.30-0.50 | 0.30-0.50 | 0.30-0.50 |
Connector Loss (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Splice Loss (Max) | N/A | N/A | 0.30-0.50 | 0.30-0.50 | 0.30-0.50 | 0.30-0.50 |
Splice Loss (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Reflectance (Max) | N/A | N/A | -65.00** | -65.00** | -65.00** | -65.00** |
Reflectance (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
(#) APC style connectors aren't used in combination with multi-mode fibers.
(**) For older generations (existing) APC connections, a value of -55.00dB may be more appropriate.