Introduction
Loss and length testing in accordance to ISO/IEC 14763-3 requires the use of test reference cords.
Furthermore, test reference cords and the 1-jumper reference should be used to ensure maximum test accuracy.
The Fluke Network CertiFiber Pro optical loss test set (OLTS) comes standard with all accesories needed to test LC-to-LC fiber optic links.
Solution
In those cases where you need to test not only LC-to-LC but also SC-to-SC and SC-to-LC fiber optic links, you need to acquire the accessories listed below.
Further information on how to use these accessories can be found in the Certiffied Cable Test Technican program.
| Product | Model | Description | Included with tester | Required for testing (LC-to-LC and SC-to-SC) | Required for testing (LC-to-LC, SC-to-SC and LC-to-SC) |
| 2635936 | NFA-LC | LC Test Adapter Set of Two | 1 | 1 | 1 |
| 4320193 | MRC-50-EFC-SCLC | Multimode EF TRC 2m 50µ (2xLC/LC, 2xSC/LC) | 1 | 1 | 2 |
| 4335564 | SRC-9-SCLC-KIT | Singlemode TRC Kit 2m (2xLC/LC, 2xSC/LC) | 1 | 1 | 2 |
| 2635929 | NFA-SC | SC Test Adapter Set of Two | 0 | 1 | 1 |
| 4320187 | MRC-50-EFC-SCSC | Multimode EF TRC 2m 50µ (4xSC/SC) | 0 | 1 | 2 |
| 4334464 | SRC-9-SCSC-KIT | Singlemode TRC Kit 2m (4xSC/SC) | 0 | 1 | 2 |
Don't forget that TRC are consumables and subject to deterioration in case they have to be replaced.
+--------------+ +--------------+