OptiFiber Pro custom test limit: Difference between revisions
Jump to navigation
Jump to search
No edit summary |
No edit summary |
||
Line 2: | Line 2: | ||
== Introduction == | == Introduction == | ||
As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. | As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. Using recent ISO and ANSI test limits is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in datacenters. | ||
| | ||
Line 8: | Line 8: | ||
== Solution == | == Solution == | ||
Unless specified otherwise, use these values to create one custom limit for testing PC/UPC terminated links and a second custom limit for testing APC terminated links. These limits mimic the limits proposed in our article [[CertiFiber_Pro_custom_test_limit]]. | Unless specified otherwise, use these values to create one custom limit for testing PC/UPC terminated links and a second custom limit for testing APC terminated links. These limits mimic the limits proposed in our article [[CertiFiber_Pro_custom_test_limit|CertiFiber_Pro_custom_test_limit]]. | ||
| |
Revision as of 19:02, 15 January 2019
Introduction
As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. Using recent ISO and ANSI test limits is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in datacenters.
Solution
Unless specified otherwise, use these values to create one custom limit for testing PC/UPC terminated links and a second custom limit for testing APC terminated links. These limits mimic the limits proposed in our article CertiFiber_Pro_custom_test_limit.
Maximum length for PC, UPC and APC terminated links
Parameter (m) | Recommended value |
---|---|
Length | N/A |
General Settings for PC, UPC and APC terminated links
Parameter | 850nm | 1300nm | 1310nm | 1490nm | 1550nm | 1625nm |
---|---|---|---|---|---|---|
Overall Loss (Max) (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
Overall Loss (Min) (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
Optical Return Loss (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
Segment Attenuation Coefficient (Max) (dB/km) | 3.0 | 1.5 | 1.0 | 1.0 | 1.0 | 1.0 |
Segment Attenuation Coefficient (Min) (dB/km) | N/A | N/A | N/A | N/A | N/A | N/A |
Event Settings for PC and UPC terminated links
Parameter (dB) | 850nm | 1300nm | 1310nm | 1490nm | 1550nm | 1625nm |
---|---|---|---|---|---|---|
Connector Loss (Max) | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 |
Connector Loss (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Splice Loss (Max) | 0.15 | 0.15 | 0.15 | 0.15 | 0.15 | 0.15 |
Splice Loss (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Reflectance (Max) | -35.00 | -35.00 | -45.00 | -45.00 | -45.00 | -45.00 |
Reflectance (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Event Settings for APC terminated links
Parameter (dB) | 850nm* | 1300nm* | 1310nm | 1490nm | 1550nm | 1625nm |
---|---|---|---|---|---|---|
Connector Loss (Max) | 0.30 | 0.30 | 0.30 | 0.30 | ||
Connector Loss (Min) | N/A | N/A | N/A | N/A | ||
Splice Loss (Max) | 0.30 | 0.30 | 0.30 | 0.30 | ||
Splice Loss (Min) | N/A | N/A | N/A | N/A | ||
Reflectance (Max) | -65.00 | -65.00 | -65.00 | -65.00 | ||
Reflectance (Min) | N/A | N/A | N/A | N/A |
(*) APC style connectors aren't used on multi-mode fiber links. You may decide to keep the default values for multi-mode wavelengths.