CertiFiber Pro test reference cords: Difference between revisions

From wiki.comcert.com
Jump to navigation Jump to search
No edit summary
No edit summary
Line 11: Line 11:


=== Solution ===
=== Solution ===
=== Accessories ===


In those cases where you need to test not only LC-to-LC but also SC-to-SC and SC-to-LC fiber optic links, you need to acquire the accessories listed below.
In those cases where you need to test not only LC-to-LC but also SC-to-SC and SC-to-LC fiber optic links, you need to acquire the accessories listed below.
Line 70: Line 72:
Don't forget that TRC are consumables and subject to deterioration in case they have to be replaced.
Don't forget that TRC are consumables and subject to deterioration in case they have to be replaced.


 
=== Setting the reference ===
<pre>+--------------+                                    +--------------+                                                   
<pre>+--------------+                                    +--------------+                                                   
|    LS      |SC                                 XX|      PM      |
|    LS      |SC---------------------------------XX|      PM      |
+--------------+                                    +--------------+  
+--------------+                                    +--------------+  


Line 79: Line 81:
                     XX-----------------------YY
                     XX-----------------------YY


&nbsp;                  XX-----------------------YY
                    XX-----------------------YY






+--------------+                                      +--------------+  
+--------------+                                      +--------------+  
|    PM      |YY                                 SC|      LS      |  
|    PM      |YY----------------------------------SC|      LS      |  
+--------------+                                      +--------------+  
+--------------+                                      +--------------+  
</pre>
</pre>

Revision as of 16:50, 14 September 2017

Introduction

Loss and length testing in accordance to ISO/IEC 14763-3 requires the use of test reference cords. 

Furthermore, test reference cords and the 1-jumper reference should be used to ensure maximum test accuracy.

The Fluke Network CertiFiber Pro optical loss test set (OLTS) comes standard with all accesories needed to test LC-to-LC fiber optic links.

 

Solution

Accessories

In those cases where you need to test not only LC-to-LC but also SC-to-SC and SC-to-LC fiber optic links, you need to acquire the accessories listed below.

Further information on how to use these accessories can be found in the Certiffied Cable Test Technican program.

Product Model Description Included with tester Required for testing (LC-to-LC and SC-to-SC) Required for testing (LC-to-LC, SC-to-SC and LC-to-SC)
2635936 NFA-LC LC Test Adapter Set of Two 1 1 1
4320193 MRC-50-EFC-SCLC Multimode EF TRC 2m 50µ (2xLC/LC, 2xSC/LC) 1 1 2
4335564 SRC-9-SCLC-KIT Singlemode TRC Kit 2m (2xLC/LC, 2xSC/LC) 1 1 2
2635929 NFA-SC SC Test Adapter Set of Two 0 1 1
4320187 MRC-50-EFC-SCSC Multimode EF TRC 2m 50µ (4xSC/SC) 0 1 2
4334464 SRC-9-SCSC-KIT Singlemode TRC Kit 2m (4xSC/SC) 0 1 2

Don't forget that TRC are consumables and subject to deterioration in case they have to be replaced.

Setting the reference

+--------------+                                     +--------------+                                                  
|     LS       |SC---------------------------------XX|      PM      |
+--------------+                                     +--------------+ 



                    XX-----------------------YY

                    XX-----------------------YY



+--------------+                                      +--------------+ 
|     PM       |YY----------------------------------SC|      LS      | 
+--------------+                                      +--------------+