OptiFiber Pro custom test limit: Difference between revisions
Jump to navigation
Jump to search
No edit summary |
No edit summary |
||
Line 2: | Line 2: | ||
== Introduction == | == Introduction == | ||
As application limits | As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. This is especially problematic when testing multi-mode firber optic links with more than two connections. | ||
| |
Revision as of 18:55, 15 January 2019
Introduction
As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. This is especially problematic when testing multi-mode firber optic links with more than two connections.
Solution
Unless specified otherwise, use these values to create one custom limit for testing PC/UPC terminated links and a second custom limit for testing APC terminated links.
Maximum length for PC, UPC and APC terminated links
Parameter (m) | Recommended value |
---|---|
Length | N/A |
General Settings for PC, UPC and APC terminated links
Parameter | 850nm | 1300nm | 1310nm | 1490nm | 1550nm | 1625nm |
---|---|---|---|---|---|---|
Overall Loss (Max) (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
Overall Loss (Min) (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
Optical Return Loss (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
Segment Attenuation Coefficient (Max) (dB/km) | 3.0 | 1.5 | 1.0 | 1.0 | 1.0 | 1.0 |
Segment Attenuation Coefficient (Min) (dB/km) | N/A | N/A | N/A | N/A | N/A | N/A |
Event Settings for PC and UPC terminated links
Parameter (dB) | 850nm | 1300nm | 1310nm | 1490nm | 1550nm | 1625nm |
---|---|---|---|---|---|---|
Connector Loss (Max) | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 | 0.30 |
Connector Loss (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Splice Loss (Max) | 0.15 | 0.15 | 0.15 | 0.15 | 0.15 | 0.15 |
Splice Loss (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Reflectance (Max) | -35.00 | -35.00 | -45.00 | -45.00 | -45.00 | -45.00 |
Reflectance (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
Event Settings for APC terminated links
Parameter (dB) | 850nm* | 1300nm* | 1310nm | 1490nm | 1550nm | 1625nm |
---|---|---|---|---|---|---|
Connector Loss (Max) | 0.30 | 0.30 | 0.30 | 0.30 | ||
Connector Loss (Min) | N/A | N/A | N/A | N/A | ||
Splice Loss (Max) | 0.30 | 0.30 | 0.30 | 0.30 | ||
Splice Loss (Min) | N/A | N/A | N/A | N/A | ||
Reflectance (Max) | -65.00 | -65.00 | -65.00 | -65.00 | ||
Reflectance (Min) | N/A | N/A | N/A | N/A |
(*) APC style connectors aren't used on multi-mode fiber links. You may decide to keep the default values for multi-mode wavelengths.