CertiFiber Pro custom test limit: Difference between revisions
Jump to navigation
Jump to search
No edit summary |
No edit summary |
||
Line 2: | Line 2: | ||
== Introduction == | == Introduction == | ||
As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. This is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in datacenters. | |||
| | ||
Line 10: | Line 10: | ||
We recommend this custom limit during length/loss testing. End-users could set Maximum Length and Maximum Overall Loss in accordance with the application limit. For example, if the link is OM3 multimode fiber and the application is IEEE 10GBASE-SR, these values would be respectively 300m and 2,60dB (@ 850 nm). More information is available during the Certified Cabling Test Training module VERSIVFO. | We recommend this custom limit during length/loss testing. End-users could set Maximum Length and Maximum Overall Loss in accordance with the application limit. For example, if the link is OM3 multimode fiber and the application is IEEE 10GBASE-SR, these values would be respectively 300m and 2,60dB (@ 850 nm). More information is available during the Certified Cabling Test Training module VERSIVFO. | ||
{| | {| style="width: 500px" cellspacing="1" cellpadding="1" border="1" | ||
|- | |- | ||
| Parameter | | Parameter |
Revision as of 18:59, 15 January 2019
Introduction
As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. This is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in datacenters.
Solution
We recommend this custom limit during length/loss testing. End-users could set Maximum Length and Maximum Overall Loss in accordance with the application limit. For example, if the link is OM3 multimode fiber and the application is IEEE 10GBASE-SR, these values would be respectively 300m and 2,60dB (@ 850 nm). More information is available during the Certified Cabling Test Training module VERSIVFO.
Parameter | Default value | Recommended value |
Length (m) | 2000,0 | 2000,0 |
Connection Loss (dB) | 0,75 | 0,30 |
Splice Loss (dB) | 0,30 | 0,15 |
Loss/km @ 850nm (dB/km) | 3,00 | 3,00 |
Loss/km @ 1300nm (dB/km) | 1,50 | 1,50 |
Loss/km @ 1310nm (dB/km) | 1,00 | 1,00 |
Loss/km @ 1550nm (dB/km) | 1,00 | 1,00 |