CertiFiber Pro test reference cords: Difference between revisions
No edit summary |
No edit summary |
||
Line 2: | Line 2: | ||
== Introduction == | == Introduction == | ||
Loss/length testing in accordance to ISO/IEC 14763-3:2014 requires the use of Test Reference Cords (TRC). TRC have less Insertion Loss (IL) in comparison to off the shelf patch cords. Furthermore, TRC and the 1-jumper reference should be used to ensure maximum test accuracy. The Fluke Network CertiFiber Pro optical loss test set (OLTS) comes with TRC and adapters required to properly test LC-to-LC fiber optic links. | Loss/length testing in accordance to ISO/IEC 14763-3:2014 requires the use of Test Reference Cords (TRC). TRC have much less Insertion Loss (IL) in comparison to off the shelf patch cords. Furthermore, TRC and the 1-jumper reference should be used to ensure maximum test accuracy and is required by the majority of fiber optic manufacturers. The Fluke Network CertiFiber Pro optical loss test set (OLTS) comes with TRC and adapters required to properly test LC-to-LC fiber optic links. | ||
| | ||
Line 10: | Line 10: | ||
=== Fluke Networks Accessories === | === Fluke Networks Accessories === | ||
In those cases where you need to test not only LC-to-LC but also SC-to-SC or SC-to-LC fiber optic links, you need to purchase | In those cases where you need to test not only LC-to-LC but also SC-to-SC or SC-to-LC fiber optic links, you need to purchase accessories. | ||
Detailed information on how to use these accessories is or will be explained during the Certified Cable Test Training VERSIVFO module. | |||
{| border="1" cellpadding="1" cellspacing="1" style="width: 1200px;" | {| border="1" cellpadding="1" cellspacing="1" style="width: 1200px;" |
Revision as of 11:27, 31 January 2021
Introduction
Loss/length testing in accordance to ISO/IEC 14763-3:2014 requires the use of Test Reference Cords (TRC). TRC have much less Insertion Loss (IL) in comparison to off the shelf patch cords. Furthermore, TRC and the 1-jumper reference should be used to ensure maximum test accuracy and is required by the majority of fiber optic manufacturers. The Fluke Network CertiFiber Pro optical loss test set (OLTS) comes with TRC and adapters required to properly test LC-to-LC fiber optic links.
Solution
Fluke Networks Accessories
In those cases where you need to test not only LC-to-LC but also SC-to-SC or SC-to-LC fiber optic links, you need to purchase accessories.
Detailed information on how to use these accessories is or will be explained during the Certified Cable Test Training VERSIVFO module.
Product | Model | Description | Included with tester | Needed for testing (LC-to-LC and SC-to-SC) | Needed for testing (LC-to-LC, SC-to-SC and LC-to-SC) |
2635934 |
NFA-LC | Set of LC Test Adapters (2) | 1 | 1 | 1 |
4320262 | MRC-50EFC-SCLCKIT (*) | Multimode Encircled Flux (EF) Test Reference Cord (TRC) kit for testing 50µm LC Fibers | 1 | 1 | 2 |
4335564 | SRC-9-SCLC-KIT (*) | Singlemode Test Reference Cord (TRC) Kit, 2m, (2) SC/LC, (2) LC/LC | 1 | 1 | 2 |
2635929 |
NFA-SC | SC Test Adapter Set of Two | 0 | 1 | 1 |
4322705 | MRC-50EFC-SCSCKIT (*) | Multimode Encircled Flux (EF) Test Reference Cord (TRC) kit for testing 50µm SC Fibers | 0 | 1 | 1 |
4334464 | SRC-9-SCSC-KIT (*) | Singlemode Test Reference Cord (TRC) Kit, 2m, (4) SC/SC | 0 | 1 | 1 |
(*) This is a consumable. In accordance to ISO/IEC 61300-2-2, the mechanical endurance (durability) of the connecting hardware shall be ≥500 cycles:
- LC typical 500 to 1000 cycles
- SC typical 2000 to 5000 cycles