OptiFiber Pro custom test limit: Difference between revisions
No edit summary |
No edit summary |
||
| Line 2: | Line 2: | ||
== Introduction == | == Introduction == | ||
While application limits continue to be more and more stringent, the test limits proposed by ISO and ANSI have hardly changed and are no longer in line with the current state of technology. | |||
Using ISO/IEC or ANSI/TIA test limits is especially problematic when testing multi-segment multi-mode fiber optic links, frequently in use in datacenters. | |||
When using ISO/IEC or ANSI/TIA test limits, it becomes increasingly more difficult for consultants to evaluate the workmanship of the installer, one of the main reasons to certify a fiber optic plant in the first place. | |||
== Solution == | == Solution == | ||
We | We recommend upgrading to the latest firmware version before continuing. Use the values below to create a custom limit for OTDR testing of multi-mode and single mode fiber optic links. | ||
Please be aware that APC connections are non-reflective and likely to be identified by the OTDR as splices. In that case, you must assist the OTDR in applying the correct limit for connector loss. | |||
=== Maximum length | === Maximum length === | ||
{| border="1" cellpadding="1" cellspacing="1" style="width: 800px" | {| border="1" cellpadding="1" cellspacing="1" style="width: 800px" | ||
| Line 23: | Line 25: | ||
|} | |} | ||
=== General Settings === | |||
=== General Settings | |||
{| border="1" cellpadding="1" cellspacing="1" style="width: 800px" | {| border="1" cellpadding="1" cellspacing="1" style="width: 800px" | ||
| Line 78: | Line 78: | ||
|} | |} | ||
(*) Accurate measurements of Segment Attenuation Coefficient requires a long fiber. Therefore, it is recommended to set this limit to N/A (not applicable) for multi-mode and short | (*) Accurate measurements of Segment Attenuation Coefficient requires a long fiber to be tested. Therefore, it is recommended to set this limit to N/A (not applicable) for multi-mode and short single mode segments. If you must specify a limit on short links, use the recommended values between brackets, but please try to explain to your customer/supplier why this is not such a good idea. | ||
=== Event Settings | === Event Settings === | ||
{| border="1" cellpadding="1" cellspacing="1" style="width: 800px" | {| border="1" cellpadding="1" cellspacing="1" style="width: 800px" | ||
| Line 95: | Line 93: | ||
|- | |- | ||
| Connector Loss (Max) | | Connector Loss (Max) | ||
| style="text-align: right" | 0. | | style="text-align: right" | 0.35-0.50 | ||
| style="text-align: right" | 0. | | style="text-align: right" | 0.35-0.50 | ||
| style="text-align: right" | 0. | | style="text-align: right" | 0.35-0.50 | ||
| style="text-align: right" | 0. | | style="text-align: right" | 0.35-0.50 | ||
| style="text-align: right" | 0. | | style="text-align: right" | 0.35-0.50 | ||
| style="text-align: right" | 0. | | style="text-align: right" | 0.35-0.50 | ||
|- | |- | ||
| Connector Loss (Min) | | Connector Loss (Min) | ||
| Line 129: | Line 127: | ||
| style="text-align: right" | -35.00 | | style="text-align: right" | -35.00 | ||
| style="text-align: right" | -35.00 | | style="text-align: right" | -35.00 | ||
| style="text-align: right" | - | | style="text-align: right" | -55.00 | ||
| style="text-align: right" | - | | style="text-align: right" | -55.00 | ||
| style="text-align: right" | - | | style="text-align: right" | -55.00 | ||
| style="text-align: right" | - | | style="text-align: right" | -55.00 | ||
|- | |- | ||
| Reflectance (Min) | | Reflectance (Min) | ||
| Line 143: | Line 141: | ||
|} | |} | ||
=== APC OTDR === | |||
When performing OTDR testing on a single mode link, the OptiFiber Pro offers the possibility to change the identity of a non-reflective event type: | |||
Revision as of 16:21, 8 April 2025
Introduction
While application limits continue to be more and more stringent, the test limits proposed by ISO and ANSI have hardly changed and are no longer in line with the current state of technology.
Using ISO/IEC or ANSI/TIA test limits is especially problematic when testing multi-segment multi-mode fiber optic links, frequently in use in datacenters.
When using ISO/IEC or ANSI/TIA test limits, it becomes increasingly more difficult for consultants to evaluate the workmanship of the installer, one of the main reasons to certify a fiber optic plant in the first place.
Solution
We recommend upgrading to the latest firmware version before continuing. Use the values below to create a custom limit for OTDR testing of multi-mode and single mode fiber optic links.
Please be aware that APC connections are non-reflective and likely to be identified by the OTDR as splices. In that case, you must assist the OTDR in applying the correct limit for connector loss.
Maximum length
| Parameter (m) | Recommended value |
|---|---|
| Length | N/A |
General Settings
| Parameter | 850nm | 1300nm | 1310nm | 1490nm | 1550nm | 1625nm |
|---|---|---|---|---|---|---|
| Overall Loss (Max) (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
| Overall Loss (Min) (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
| Optical Return Loss (dB) | N/A | N/A | N/A | N/A | N/A | N/A |
| Segment Attenuation Coefficient* (Max) (dB/km) | N/A (3.0) | N/A (1.5) | N/A (0.4) | N/A (0.4) | N/A (0.4) | N/A (0.4) |
| Segment Attenuation Coefficient (Min) (dB/km) | N/A | N/A | N/A | N/A | N/A | N/A |
(*) Accurate measurements of Segment Attenuation Coefficient requires a long fiber to be tested. Therefore, it is recommended to set this limit to N/A (not applicable) for multi-mode and short single mode segments. If you must specify a limit on short links, use the recommended values between brackets, but please try to explain to your customer/supplier why this is not such a good idea.
Event Settings
| Parameter (dB) | 850nm | 1300nm | 1310nm | 1490nm | 1550nm | 1625nm |
|---|---|---|---|---|---|---|
| Connector Loss (Max) | 0.35-0.50 | 0.35-0.50 | 0.35-0.50 | 0.35-0.50 | 0.35-0.50 | 0.35-0.50 |
| Connector Loss (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
| Splice Loss (Max) | 0.15 | 0.15 | 0.15 | 0.15 | 0.15 | 0.15 |
| Splice Loss (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
| Reflectance (Max) | -35.00 | -35.00 | -55.00 | -55.00 | -55.00 | -55.00 |
| Reflectance (Min) | N/A | N/A | N/A | N/A | N/A | N/A |
APC OTDR
When performing OTDR testing on a single mode link, the OptiFiber Pro offers the possibility to change the identity of a non-reflective event type: