CertiFiber Pro test reference cords

From wiki.comcert.com
Revision as of 06:22, 21 September 2017 by Bert (talk | contribs)
Jump to navigation Jump to search

Introduction

Loss/length testing in accordance to ISO/IEC 14763-3:2014 requires the use of Test Reference Cords (TRC). Especially multi-mode TRC have much less Insertion Loss (IL) in comparison to off the shelf patch cords. Furthermore, TRC and the 1-jumper reference should be used to ensure maximum test accuracy. The Fluke Network CertiFiber Pro optical loss test set (OLTS) comes with TRC and adapters required to properly test LC-to-LC fiber optic links.

 

Solution

Fluke Networks Accessories

In those cases where you need to test not only LC-to-LC but also SC-to-SC or SC-to-LC fiber optic links, you need to purchase the accessories listed below.

Further information on how to use these accessories will be explained during the Certified Cable Test Training VERSIVFO module.

Product Model Description Included with tester Required for testing (LC-to-LC and SC-to-SC) Required for testing (LC-to-LC, SC-to-SC and LC-to-SC)

2635934

NFA-LC Set of LC Test Adapters (2) 1 1 1
4320262 MRC-50EFC-SCLCKIT (*) Multimode Encircled Flux (EF) Test Reference Cord (TRC) kit for testing 50µm LC Fibers 1 1 2
4335564 SRC-9-SCLC-KIT (*) Singlemode Test Reference Cord (TRC) Kit, 2m, (2) SC/LC, (2) LC/LC 1 1 2

2635929

NFA-SC SC Test Adapter Set of Two 0 1 1
4322705 MRC-50EFC-SCSCKIT (*) Multimode Encircled Flux (EF) Test Reference Cord (TRC) kit for testing 50µm SC Fibers 0 1 1
4334464 SRC-9-SCSC-KIT (*) Singlemode Test Reference Cord (TRC) Kit, 2m, (4) SC/SC 0 1 1

(*) This is a consumable. In accordance to ISO/IEC 61300-2-2, the mechanical endurance (durability) of the connecting hardware shall be ≥500 cycles:

  • LC typical 500 to 1000 cycles
  • SC typical 2000 to 5000 cycles