CertiFiber Pro custom test limit
Introduction
As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. Using recent ISO and ANSI test limits is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in data centers.
Solution
Use this custom limit for length/loss testing of LC, SC, ST, FC and E2000 terminated fiber optic links. We cannot and will not advise as to what is a suitable test limit for MPO/MTP. You must consult with the designer of that cabling system.
Users could set optional Maximum Length and Maximum Overall Loss limits in accordance with the application. For example: if the link is OM3 multimode fiber and the application is IEEE 10GBASE-SR, these values would be respectively 300m and 2,60dB (@ 850nm).
More information on the use of custom limits is available during the Certified Cabling Test Training module VERSIVFO.
Parameter | Default value | Recommended value |
Length (m) | 2000,0 | 2000,0 |
Connection Loss (dB) | 0,75 | 0,30 |
Splice Loss (dB) | 0,30 | 0,15 |
Loss/km @ 850nm (dB/km) | 3,00 | 3,00 |
Loss/km @ 1300nm (dB/km) | 1,50 | 1,50 |
Loss/km @ 1310nm (dB/km) | 1,00 | 1,00 |
Loss/km @ 1550nm (dB/km) | 1,00 | 1,00 |