OptiFiber Pro custom test limit: Difference between revisions

From wiki.comcert.com
Jump to navigation Jump to search
No edit summary
No edit summary
Line 62: Line 62:
|-
|-
| Segment Attenuation Coefficient (Max) (dB/km)*
| Segment Attenuation Coefficient (Max) (dB/km)*
| style="text-align: right" | 3.0
| style="text-align: right" | N/A (3.0)
| style="text-align: right" | 1.5
| style="text-align: right" | N/A (1.5)
| style="text-align: right" | 1.0
| style="text-align: right" | N/A (1.0)
| style="text-align: right" | 1.0
| style="text-align: right" | N/A (1.0)
| style="text-align: right" | 1.0
| style="text-align: right" | N/A (1.0)
| style="text-align: right" | 1.0
| style="text-align: right" | N/A (1.0)
|-
|-
| Segment Attenuation Coefficient (Min) (dB/km)
| Segment Attenuation Coefficient (Min) (dB/km)
Line 78: Line 78:
|}
|}


*Accurate measurement of Segment Attenuation Coefficient requires a significant length of fiber.  Don't set this limit for short links.  
(*) Accurate measurements of Segment Attenuation Coefficient requires a significant length of fiber. Don't use this limit on short links.  If you must use this limit, use values between brackets.


 
 

Revision as of 10:13, 27 October 2019

Introduction

As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. Using recent ISO and ANSI test limits is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in datacenters.

 

Solution

We stronly recommend upgrading to Versiv firmware version 6 before continuing.  Unless specified otherwise, use these values to create one custom limit for testing PC/UPC terminated links and a second custom limit for testing APC terminated links.  Please remember that in case of OTDR, "Connector Loss" should be interpreted as "Reflective Event Loss" and "Splice Loss" as "Non reflective Event Loss".

 

Maximum length for PC, UPC and APC terminated links

Parameter (m) Recommended value
Length N/A

 

General Settings for PC, UPC and APC terminated links

Parameter 850nm 1300nm 1310nm 1490nm 1550nm 1625nm
Overall Loss (Max) (dB) N/A N/A N/A N/A N/A N/A
Overall Loss (Min) (dB) N/A N/A N/A N/A N/A N/A
Optical Return Loss (dB) N/A N/A N/A N/A N/A N/A
Segment Attenuation Coefficient (Max) (dB/km)* N/A (3.0) N/A (1.5) N/A (1.0) N/A (1.0) N/A (1.0) N/A (1.0)
Segment Attenuation Coefficient (Min) (dB/km) N/A N/A N/A N/A N/A N/A

(*) Accurate measurements of Segment Attenuation Coefficient requires a significant length of fiber. Don't use this limit on short links. If you must use this limit, use values between brackets.

 

Event Settings for PC and UPC terminated links

Parameter (dB) 850nm 1300nm 1310nm 1490nm 1550nm 1625nm
Connector Loss (Max) 0.30-0.50 0.30-0.50 0.30-0.50 0.30-0.50 0.30-0.50 0.30-0.50
Connector Loss (Min) N/A N/A N/A N/A N/A N/A
Splice Loss (Max) 0.15 0.15 0.15 0.15 0.15 0.15
Splice Loss (Min) N/A N/A N/A N/A N/A N/A
Reflectance (Max) -35.00 -35.00 -45.00 -45.00 -45.00 -45.00
Reflectance (Min) N/A N/A N/A N/A N/A N/A

 

Event Settings for APC terminated links

Parameter (dB) 850nm# 1300nm# 1310nm 1490nm 1550nm 1625nm
Connector Loss (Max)     0.30-0.50 0.30-0.50 0.30-0.50 0.30-0.50
Connector Loss (Min)     N/A N/A N/A N/A
Splice Loss (Max)*     0.30-0.50 0.30-0.50 0.30-0.50 0.30-0.50
Splice Loss (Min)     N/A N/A N/A N/A
Reflectance (Max)     -65.00 -65.00 -65.00 -65.00
Reflectance (Min)     N/A N/A N/A N/A

# APC style connectors aren't used on multi-mode fiber links. You may decide to keep the default values for these multi-mode wavelengths.