== Introduction ==
== Introduction ==


Limits specified by ISO/IEC11801:2017 and ISO/IEC14763-3:2014 (Information technology -- Implementation and operation of customer premises cabling -- Part 3: Testing of optical fibre cabling) are no longer adequate to evaluate the quality of recently installed fiber optic infrastructure.
As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. Using recent ISO and ANSI test limits is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in datacenters.
 
This article was recently updated for firmware version 6.0 (January 2019).


 
 
Line 10: Line 8:
== Solution ==
== Solution ==


Unless specified otherwise, use these values to create one custom limit for testing PC/UPC terminated links and a second custom limit for testing APC terminated links.
We stronly recommend upgrading to Versiv firmware version 6.8 before continuing.  Unless specified otherwise, use these values to create one custom limit for testing PC/UPC terminated links and a second custom limit for testing APC terminated links.  Please remember that in case of OTDR, "Connector Loss" should be interpreted as "Reflective Event Loss" and "Splice Loss" as "Non reflective Event Loss".


 
 
Line 16: Line 14:
=== Maximum length for <span style="background-color:#00FFFF">PC</span>, <span style="background-color:#00FFFF">UPC</span> and <span style="background-color:#FFFF00">APC</span> terminated links ===
=== Maximum length for <span style="background-color:#00FFFF">PC</span>, <span style="background-color:#00FFFF">UPC</span> and <span style="background-color:#FFFF00">APC</span> terminated links ===


{| style="width: 800px" cellspacing="1" cellpadding="1" border="1"
{| border="1" cellpadding="1" cellspacing="1" style="width: 800px"
|-
|-
! scope="col" style="width: 332px" | Parameter (m)
! scope="col" style="width: 332px" | Parameter (m)
Line 22: Line 20:
|-
|-
| style="width: 332px" | Length
| style="width: 332px" | Length
| style="width: 455px; text-align: right" | N/A
| style="width: 455px; text-align: right" | N/A
|}
|}


Line 29: Line 27:
=== General Settings for <span style="background-color:#00FFFF">PC</span>, <span style="background-color:#00FFFF">UPC</span> and <span style="background-color:#FFFF00">APC</span> terminated links ===
=== General Settings for <span style="background-color:#00FFFF">PC</span>, <span style="background-color:#00FFFF">UPC</span> and <span style="background-color:#FFFF00">APC</span> terminated links ===


{| style="width: 800px" cellspacing="1" cellpadding="1" border="1"
{| border="1" cellpadding="1" cellspacing="1" style="width: 800px"
|-
|-
! scope="col" | Parameter
! scope="col" | Parameter
Line 63: Line 61:
| style="text-align: right" | N/A
| style="text-align: right" | N/A
|-
|-
| Segment Attenuation Coefficient (Max) (dB/km)
| Segment Attenuation Coefficient* (Max) (dB/km)
| style="text-align: right" | 3.0
| style="text-align: right" | N/A (3.0)
| style="text-align: right" | 1.5
| style="text-align: right" | N/A (1.5)
| style="text-align: right" | 1.0
| style="text-align: right" | N/A (0.4)
| style="text-align: right" | 1.0
| style="text-align: right" | N/A (0.4)
| style="text-align: right" | 1.0
| style="text-align: right" | N/A (0.4)
| style="text-align: right" | 1.0
| style="text-align: right" | N/A (0.4)
|-
|-
| Segment Attenuation Coefficient (Min) (dB/km)
| Segment Attenuation Coefficient (Min) (dB/km)
Line 79: Line 77:
| style="text-align: right" | N/A
| style="text-align: right" | N/A
|}
|}
(*) Accurate measurements of Segment Attenuation Coefficient requires a long fiber. Therefore, it is recommended to set this limit to N/A (not applicable) for multi-mode and short singlemode segments. If you have to enforce a&nbsp;limit, use the recommended values between brackets, but first try to explain to your customer/supplier why this is not a good idea.


&nbsp;
&nbsp;


=== Event Settings for <span style="background-color:#00FFFF">PC</span> and <span style="background-color:#00FFFF">UPC</span> terminated links ===
=== Event Settings for <span style="background-color:#00FFFF">PC</span><span style="background-color:#00FFFF">/UPC</span> terminated links ===


{| style="width: 800px" cellspacing="1" cellpadding="1" border="1"
{| border="1" cellpadding="1" cellspacing="1" style="width: 800px"
|-
|-
! scope="col" | Parameter (dB)
! scope="col" | Parameter (dB)
Line 95: Line 95:
|-
|-
| Connector Loss (Max)
| Connector Loss (Max)
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
|-
|-
| Connector Loss (Min)
| Connector Loss (Min)
Line 147: Line 147:
=== Event Settings for <span style="background-color:#FFFF00">APC</span> terminated links ===
=== Event Settings for <span style="background-color:#FFFF00">APC</span> terminated links ===


{| style="width: 800px" cellspacing="1" cellpadding="1" border="1"
{| border="1" cellpadding="1" cellspacing="1" style="width: 800px"
|-
|-
! scope="col" | Parameter (dB)
! scope="col" | Parameter (dB)
! scope="col" | 850nm*
! scope="col" | 850nm<sup>#</sup>
! scope="col" | 1300nm*
! scope="col" | 1300nm<sup>#</sup>
! scope="col" | 1310nm
! scope="col" | 1310nm
! scope="col" | 1490nm
! scope="col" | 1490nm
Line 158: Line 158:
|-
|-
| Connector Loss (Max)
| Connector Loss (Max)
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
|-
|-
| Connector Loss (Min)
| Connector Loss (Min)
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | N/A
| style="text-align: right" | N/A
| style="text-align: right" | N/A
| style="text-align: right" | N/A
Line 174: Line 174:
|-
|-
| Splice Loss (Max)
| Splice Loss (Max)
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
| style="text-align: right" | 0.30
| style="text-align: right" | 0.30-0.50
|-
|-
| Splice Loss (Min)
| Splice Loss (Min)
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | N/A
| style="text-align: right" | N/A
| style="text-align: right" | N/A
| style="text-align: right" | N/A
Line 190: Line 190:
|-
|-
| Reflectance (Max)
| Reflectance (Max)
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | -65.00
| style="text-align: right" | -65.00**
| style="text-align: right" | -65.00
| style="text-align: right" | -65.00**
| style="text-align: right" | -65.00
| style="text-align: right" | -65.00**
| style="text-align: right" | -65.00
| style="text-align: right" | -65.00**
|-
|-
| Reflectance (Min)
| Reflectance (Min)
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | &nbsp;
| style="text-align: right" | N/A
| style="text-align: right" | N/A
| style="text-align: right" | N/A
| style="text-align: right" | N/A
| style="text-align: right" | N/A
Line 206: Line 206:
|}
|}


(*) APC style connectors aren't used on multi-mode fiber links. You may decide to keep the default values for multi-mode wavelengths.
(#) APC style connectors aren't used in combination with&nbsp;multi-mode fibers.
 
(**) For older generations (existing) APC connections, a value of -55.00dB may be more appropriate.

Latest revision as of 12:22, 25 August 2023

Introduction

As application limits continue to become more stringent, limits proposed by ISO and ANSI are no longer acceptable to evaluate the quality of a fiber optic infrastructure. Using recent ISO and ANSI test limits is especially problematic when testing multi-mode fiber optic links with more than two connections, which is often the case in datacenters.

 

Solution

We stronly recommend upgrading to Versiv firmware version 6.8 before continuing.  Unless specified otherwise, use these values to create one custom limit for testing PC/UPC terminated links and a second custom limit for testing APC terminated links.  Please remember that in case of OTDR, "Connector Loss" should be interpreted as "Reflective Event Loss" and "Splice Loss" as "Non reflective Event Loss".

 

Maximum length for PC, UPC and APC terminated links

Parameter (m) Recommended value
Length N/A

 

General Settings for PC, UPC and APC terminated links

Parameter 850nm 1300nm 1310nm 1490nm 1550nm 1625nm
Overall Loss (Max) (dB) N/A N/A N/A N/A N/A N/A
Overall Loss (Min) (dB) N/A N/A N/A N/A N/A N/A
Optical Return Loss (dB) N/A N/A N/A N/A N/A N/A
Segment Attenuation Coefficient* (Max) (dB/km) N/A (3.0) N/A (1.5) N/A (0.4) N/A (0.4) N/A (0.4) N/A (0.4)
Segment Attenuation Coefficient (Min) (dB/km) N/A N/A N/A N/A N/A N/A

(*) Accurate measurements of Segment Attenuation Coefficient requires a long fiber. Therefore, it is recommended to set this limit to N/A (not applicable) for multi-mode and short singlemode segments. If you have to enforce a limit, use the recommended values between brackets, but first try to explain to your customer/supplier why this is not a good idea.

 

Event Settings for PC/UPC terminated links

Parameter (dB) 850nm 1300nm 1310nm 1490nm 1550nm 1625nm
Connector Loss (Max) 0.30-0.50 0.30-0.50 0.30-0.50 0.30-0.50 0.30-0.50 0.30-0.50
Connector Loss (Min) N/A N/A N/A N/A N/A N/A
Splice Loss (Max) 0.15 0.15 0.15 0.15 0.15 0.15
Splice Loss (Min) N/A N/A N/A N/A N/A N/A
Reflectance (Max) -35.00 -35.00 -45.00 -45.00 -45.00 -45.00
Reflectance (Min) N/A N/A N/A N/A N/A N/A

 

Event Settings for APC terminated links

Parameter (dB) 850nm# 1300nm# 1310nm 1490nm 1550nm 1625nm
Connector Loss (Max) N/A N/A 0.30-0.50 0.30-0.50 0.30-0.50 0.30-0.50
Connector Loss (Min) N/A N/A N/A N/A N/A N/A
Splice Loss (Max) N/A N/A 0.30-0.50 0.30-0.50 0.30-0.50 0.30-0.50
Splice Loss (Min) N/A N/A N/A N/A N/A N/A
Reflectance (Max) N/A N/A -65.00** -65.00** -65.00** -65.00**
Reflectance (Min) N/A N/A N/A N/A N/A N/A

(#) APC style connectors aren't used in combination with multi-mode fibers.

(**) For older generations (existing) APC connections, a value of -55.00dB may be more appropriate.